YOU ARE HERE: Products > Distribution Switches > LineBOSS 15kV – 38kV Sidebreak GOAB Switch – Specifications
Specifications
The LineBOSS™ Sidebreak switch is the most robust, yet elegant sidebreak switch in the market today. Every LineBOSS™ component brings meaningful operator benefits for years to come. Features such as 1/4 inch steel phase base, stainless steel to brass bearings, silver plated copper reverse loop contacts and busbar blades mean efficient and smooth operation over a very long life; even in hostile environments where dust, humidity, corrosives and other industrial or natural contaminants play havoc with most. You’ll be amazed with how much switch you can buy for the money. The LBS distribution switch is RUS accepted.
Switch Ratings
Voltage Class: | Continuous Current Class: |
Fault Close: | Momentary Current: | Ice breaking: | Mechanical: |
---|---|---|---|---|---|
15.5 kV | 600 A | 15kA rms-asym: 5 X manual operation |
600 A: 40,000 A rms/65kA peak – 10 cycles 25,000 A rms 3 seconds |
3/4″ (manual operation) |
5000 cycles (open/close) |
25.8 kV | 900 A | 20kA rms-asym: 3 X manual operation |
900 A: 51,000 A rms/72kA peak – 10 cycles 32,000 A rms 3 seconds |
||
38 kV | 1200 A | 30kA rms-asym: 2 X manual operation |
1200 A: 70,000 A rms/99kA peak – *10 cycles 44,000 A rms 3 seconds |
*Inertia exceeds ANSI required of 60kA rms momentary